Smoke ventilation · D+H

Products

Technical data and documentation for the D+H smoke ventilation products we install most: control panels, drives, buttons, sensors and detectors.

01 · CPS-B · CPS-P · CPS-M

Smoke control panels

The control panel is the heart of a smoke ventilation system: it powers the drives, reads the detectors and smoke vent buttons, and opens the right zone in a fire. D+H panels run on 230 V AC and supply 24 V DC to the drives.

Request a quote

Features

  • CPS-B: compact panels for stairwells, 2.5 A or 5 A, one line and one group
  • CPS-P: for high-current applications, 10 A or 20 A, up to 16 panels networked as main and sub panels
  • CPS-M: fully modular, 20 A, 2 to 6 lines and groups, optional 3.5" colour touch panel
  • Battery backup for at least 72 hours on CPS-B and CPS-P
  • Built-in comfort functions for daily ventilation
  • CPS-B and CPS-M tested to ISO 21927-9, VdS and DIN EN 12101-10

Common data

Supply
230 V AC / 50 Hz
Drive output
24 V DC
Alarm / ventilation
30 % short-time duty
Temperature range
−5 … +40 °C

Models

ModelOutputLines / groupsProtectionW × H × D
CPS-B1-2.5-010124 V DC / 2.5 A1 / 1IP30310 × 310 × 104 mm
CPS-B1-5-010124 V DC / 5 A1 / 1IP30310 × 310 × 104 mm
CPS-P1-010-020224 V DC / 10 A2 / 2IP54300 × 350 × 165 mm
CPS-P1-020-020224 V DC / 20 A2 / 2IP54400 × 500 × 245 mm
CPS-M1-020-B24 V DC / 20 A2 / 2 to 6 / 6IP54500 × 500 × 210 mm

Documents

02 · CDC

CDC chain actuators

Compact, quiet chain drives for windows and smoke vents. They fit inside the window profile or on its surface, with universal bracket sets for all common profile systems.

Request a quote

Features

  • For smoke exhaust (D+H Euro SHEV, EN 12101-2) and daily ventilation
  • Very quiet: sound pressure level up to 35 dB(A)
  • Strokes of 350, 500, 600 and 800 mm, left and right types
  • ACB versions with a Modbus RTU bus interface for building management systems
  • TMS+ versions: tandem safety function for two drives on one sash
  • CDC-TW: two chains and 500 N, spreading the force across large sashes

Common data

Supply
24 V DC ±15 %
Duty cycle
30 % (3 min on / 7 min off)
Protection
IP32
Temperature range
−15 … +75 °C
Fire resistance
B300 (30 min / 300 °C)

03 · KA 34

KA 34 chain actuator

A robust chain drive for smoke exhaust and daily ventilation, with a high-speed mode that opens windows especially fast in a fire.

Request a quote

Features

  • For smoke exhaust (D+H Euro SHEV, EN 12101-2) and daily ventilation
  • High-speed function (HS) for fast opening in a fire
  • Special chain stabilisation: pushing strokes up to 700 mm, pulling strokes above 1000 mm possible
  • Relieves pressure on the window gasket after closing
  • Slows down to 5 mm/s when closing and reverses on an obstacle
  • Locking force up to 2600 N (2000 N according to VdS 2580)

Common data

Supply
24 V DC ±15 % / 1 A
Push / pull force
300 N
SHEV opening speed
12.2 mm/s
Protection
IP32
Temperature range
−15 … +75 °C
Fire resistance
B300 (30 min / 300 °C)

Models

ModelStrokeLengthWeight
KA 34/350350 mm421 mm1.6 kg
KA 34/500500 mm496 mm1.9 kg
KA 34/600600 mm546 mm2.2 kg
KA 34/700700 mm596 mm2.4 kg
KA 34/800800 mm646 mm2.6 kg
KA 34/10001000 mm750 mm3 kg

Documents

04 · DDS 54

DDS 54 door drive

A drive that opens single-leaf doors up to 90°, so fresh air can flow in, the smoke is pushed out and escape routes stay open.

Request a quote

Features

  • Opens single-leaf doors up to 90°
  • Supplies the air needed for smoke exhaust and keeps escape routes open
  • The door can still be opened by hand
  • Control output for an electronic door release; can be combined with Ikon or Ehem motor locks
  • Passive and active anti-trap protection on the main closing edges
  • Bracket set included

Common data

Supply
24 V DC ±15 % / 1 A
Duty cycle
30 % (3 min on / 7 min off)
Protection
IP32
Temperature range
−5 … +75 °C
Fire resistance
B300 (30 min / 300 °C)

Models

ModelPush / pull forceStrokeW × H × DWeight
DDS 54/500500 N500 mm522 × 40 × 80 mm2 kg

Documents

05 · RT 46

Smoke vent buttons

Smoke vent buttons for triggering the system by hand at exits and along escape routes. They work as main or auxiliary operation panels with all 24 V DC D+H control panels.

Request a quote

Features

  • SHEV OPEN and SHEV Reset functions
  • Main or auxiliary operation panel
  • Optional integrated ventilation button
  • Plastic or die-cast aluminium housing, in orange or yellow
  • RT 46-ACR version for ring bus systems

Common data

Input voltage
18 … 28 V DC
Protection
IP40
Temperature range
−5 … +40 °C

Models

ModelHousingColourW × H × D
RT 46PlasticOrange (~ RAL 2011)129 × 135 × 39 mm
RT 46-KDPlasticOrange (~ RAL 2011)129 × 135 × 39 mm
RT 46-ALUDie-cast aluminiumOrange (~ RAL 2011)129 × 138 × 39 mm
RT 46-ALU/YDie-cast aluminiumYellow (~ RAL 1004)129 × 138 × 39 mm
RT 46-ACRPlasticOrange (~ RAL 2011)129 × 135 × 39 mm

Documents

06 · LT 84 · WRS-S · RS-S

Ventilation controls

Buttons and weather sensors for everyday natural ventilation: open the windows when you need fresh air, and let them close by themselves when wind or rain comes.

Request a quote

Features

  • LT 84-U: ventilation OPEN / STOP / CLOSED for one group, 24 V DC
  • LT 84-U-V: the same for 230 V AC groups, with mechanically interlocked buttons
  • Flush mounting in a standard 55 mm socket (not included)
  • WRS-S wind and rain sensor and RS-S rain sensor close the windows in bad weather

Common data

Buttons
IP20, white, 80 × 80 mm
Sensors
IP44, −30 … +50 °C

Models

ModelTypeSupplyProtection
LT 84-UVentilation button24 V DCIP20
LT 84-U-VVentilation button230 V ACIP20
WRS-SWind and rain sensor24 V DC / 0.09 AIP44
RS-SRain sensor24 V DC / 0.06 AIP44

Documents

07 · SD-O 371 · FD-T 271

Smoke and heat detectors

Automatic detectors that trigger the smoke ventilation when they sense smoke or a rapid rise in temperature. Only detectors approved by D+H can be connected to D+H control panels.

Request a quote

Features

  • SD-O 371: optical smoke detector for areas up to 110 m² and heights up to 12 m
  • FD-T 271: rate-of-rise heat detector for areas up to 30 m² and heights up to 7.5 m
  • Same housing for both: white ABS, 117 mm diameter

Common data

Nominal voltage
24 V DC
Protection
IP40
Air humidity
≤ 95 %

Models

ModelTypeMonitoring areaMax. heightTemperature range
SD-O 371Optical smoke110 m²12 m−20 … +72 °C
FD-T 271Heat, rate of rise30 m²7.5 m−20 … +50 °C

Documents

08 · Accessories

Brackets and accessories

Bracket sets for every drive and window type, plus housings, power supplies and batteries. We choose the right parts for each window when we plan the system.

Request a quote

Features

  • Bracket sets matched to each drive and profile system
  • Housings and flush-mounting frames for buttons
  • Power supplies and replacement batteries for control panels
  • Detector accessories: mounting brackets, covers and protective guards

Tell us the window profile and the opening type, and we will specify the right bracket set.

Technical data and documents: D+H Mechatronic AG. Please check the latest version with us before ordering.

Need help choosing?

Send us the drawings. We will size the system.

Tell us about the building and the windows, and we will select the panels, drives and accessories and send you a quote.